kategorieë
- ons Blog (71)
- tegnologie-ondersteuning (17)
When we are talking about the design of a fire suppression system, any of these systems could design the correct extinguishing agent to protect the fire protection zone, so we need to design it by using design software on a computer and by using the design formula, hiermee gee ons 'n eenvoudige formule van aërosolbrandonderdrukkingstelsel, to help calculate how many quantities of the aerosol agent is needed for a protection zone, to help the technician to design, installasie en ontfouting die stelsel in die beskerming sone, Below are the aerosol fire suppression system calculation formula:
Byvoorbeeld:
'n kragopwekker kamer with a length of 10 meter, a width of 8 meter, and a height of 3 meter, it is designed to use a Vloer staan Aerosol Vuur Onderdrukking Device or a Wall-Mounted aerosol fire suppression device to install as a fire solution, die ontwerp program is soos hieronder:
1. Bereken die volume van die beskerming Sone:
V = L * W * H = 10 * 8 * 3 = 240 kubieke meter, So the Fa value makes it 1.0
2. Die ontwerp aansoek digtheid is gewoonlik 0.14 kilogram per kubieke meter.
3. Bereken die dosis van die aërosolmiddel in hoeveelheid (kilogram):
M = Da*Fa*V = 0,14*1,0*240 = 33,6 kilogram.
Afsluiting:
So this power generator room uses 3 stelle QRR10LW / S(10 kilogram) en 1 stel AW-QRR5LW/S(5 kilogram) om totale oorstromings as 'n brand onderdrukking oplossing vir die kamer.
The aerosol fire suppression system calculation job is so easy!
To learn more about similar knowledge please turn to die NFPA webwerf of IPV as a reference.